110.16Arc-Flash Hazard Marking

Article 110GENERAL REQUIREMENTS FOR ELECTRICAL INSTALLATIONS

110.16 - Arc-Flash Hazard Marking: The Label That Could Save Your Pretty Face

The "Don't Make Me a Statistic" Sticker

Alright, listen up. You know those orange warning labels you see slapped on panels and switchgear? The ones telling you how badly things could go south if that main breaker decides to throw a tantrum? That's 110.16, and it's there because somebody way smarter than us did the math on exactly how much "holy crap" is waiting inside that box.

Here's the deal: In commercial and industrial installations (your house doesn't count – Grandma's panel is exempt from this bureaucratic beauty), you need permanent arc-flash labels on any equipment where some poor soul might have to work on it while it's still hot. We're talking:

  • Service equipment (the big daddy gear)
  • Switchboards and switchgear (the expensive stuff)
  • Enclosed panelboards (regular Joes, but enclosed)
  • Industrial control panels (factory robot brains)
  • Meter socket enclosures (where the power company meets your wallet)
  • Motor control centers (bucket of contactors central)

If someone's likely to be poking around in there while it's energized – doing inspections, adjustments, maintenance, or just looking for where that mystery hum is coming from – it needs a label.

What Goes on This Life-Saving Sticky Note?

The label has to meet 110.21(B) requirements (that's the "make it actually readable" section), be visible to qualified persons (not hidden behind the damn door), and contain four critical pieces of intel:

  1. Nominal system voltage – Is it 120/240V or 480V three-phase trying to kill you? Inquiring minds need to know.

  2. Arc flash boundary – How far away you need to stand when things go "ZAP!" Think of it as the "splash zone" for electrons.

  3. Available incident energy OR minimum PPE level – Either "X calories per square centimeter of roasted electrician" or "You need LEVEL 2 gear, Einstein." (One or the other, not necessarily both.)

  4. Date of the assessment – Because electrical systems age like fine wine... if fine wine could suddenly explode and turn you into a Roman candle.

The label needs to follow industry standards (NFPA 70E is the popular kid here), and it has to be placed where you'll actually see it BEFORE you stick your screwdriver in there.


KEY TAKEAWAYS (The Stuff That Matters)

THE RULE:

  • WHERE: Commercial and industrial installations ONLY (dwelling units get a pass)
  • WHAT EQUIPMENT: Service equipment, switchboards, switchgear, enclosed panelboards, industrial control panels, meter enclosures, and MCCs that might be worked on energized
  • TYPE: Permanent marking (field or factory applied)
  • VISIBILITY: Must be clearly visible to qualified persons
  • COMPLIANCE: Must meet 110.21(B) marking standards

THE LABEL MUST INCLUDE:

  1. Nominal system voltage
  2. Arc flash boundary distance
  3. Available incident energy (cal/cm²) OR minimum PPE level required
  4. Date the arc-flash hazard assessment was completed

WHAT DOESN'T NEED IT:

  • ❌ Residential dwellings (houses, apartments, condos)
  • ❌ Equipment that's never serviced energized (good luck finding that unicorn)

INDUSTRY STANDARDS REFERENCED:

  • NFPA 70E (the arc-flash bible)
  • ANSI Z535.4 (label design guidelines)

REAL-WORLD JOBSITE SCENARIOS

Scenario 1: "The Mystery of the Missing Label"

You're doing a service call at a manufacturing plant. The maintenance guy says, "Yeah, we keep popping breakers in MCC-3." You walk up to this motor control center that's been there since Carter was president, and there's no arc-flash label anywhere.

The Problem: Without that label, you have NO IDEA if you need Level 1 or Level 4 PPE. Is this a "wear your safety glasses" situation or a "dress like you're defusing a bomb" situation?

What Should Happen: Before you crack that door open, somebody needs to perform an arc-flash assessment and slap a proper label on there. Not your job? Fine, but don't work it hot without knowing the hazard level. Your family wants you home with the same number of fingers you left with.

Inspector's Note: I've red-tagged jobs where expensive new gear had no labels. The contractor whined, "But we just installed it!" Doesn't matter. 110.16 says it needs a label BEFORE final inspection. Period.

Scenario 2: "The Label Time Machine"

You're troubleshooting a switchboard that's labeled... but the assessment date is from 2010. Meanwhile, they've added three new feeders, upsized the service, and probably added a flux capacitor.

The Problem: That label is a lie. The available fault current has changed, which means the incident energy has changed, which means your PPE requirements might have changed. That "Level 2" label might need to say "Level 4" now.

What Should Happen: Arc-flash assessments aren't "one and done." When you make significant changes to an electrical system, you need to recalculate and update those labels.

Real Talk: I know a guy who got caught in an arc flash wearing Level 2 gear when he needed Level 4. The label was outdated by eight years. He survived, but he's got some gnarly scars and a genuine fear of Mondays now.

Scenario 3: "The Residential Confusion"

You're wiring a 5,000 sq ft McMansion with a 400A service. The homeowner, who's a plant manager, says, "Hey, at my work we have those arc-flash labels. Shouldn't my house have one?"

The Answer: Nope! 110.16 specifically says "In other than dwelling units." Residential doesn't require arc-flash labels, even if it's a mansion with more square footage than a grocery store.

Why? Because homeowners aren't supposed to be working on their service panel while it's energized. (Yeah, I know some do anyway, but that's what YouTube liability disclaimers are for.)

Scenario 4: "The Panel That Nobody Opens"

You're installing a small enclosed panelboard in a janitor's closet. It's a subpanel with a main breaker disconnect, all 120/208V lighting circuits. Your apprentice asks, "Do we need an arc-flash label on this thing?"

The Answer: Maybe. Does this panel meet the "likely to require examination, adjustment, servicing, or maintenance while energized" test? If it's just a simple panel with breakers that never need adjustment, and it has a disconnect so you can kill it before working on it, you might be able to argue no. BUT...

Real Talk: When in doubt, put the label on. It's way cheaper than a lawsuit, and it takes five minutes. Most inspectors and safety officers would rather see labels on everything than play the "is this likely to be serviced hot?" guessing game.


WHAT TO STUDY (Exam Warriors, Pay Attention)

Master Exam Hotspots:

1. The Four Required Items on the Label (This is HUGE on exams)

  • Nominal system voltage
  • Arc flash boundary
  • Incident energy OR PPE level (understand it's "or" not "and")
  • Date of assessment

Memory Trick: Voltage, Boundary, Energy/PPE, Date = "Very Bad Energized Parts, Dude"

2. Where It Applies vs. Where It Doesn't

  • Applies: Commercial, industrial
  • Doesn't apply: Dwelling units (houses, apartments, condos)
  • They LOVE to throw dwelling unit questions at you

3. Equipment Types That Require Labels Memorize the list:

  • Service equipment
  • Switchboards
  • Switchgear
  • Enclosed panelboards
  • Industrial control panels
  • Meter socket enclosures
  • Motor control centers

4. The "While Energized" Language The phrase "likely to require examination, adjustment, servicing, or maintenance while energized" is exam gold. Questions will test whether you understand not EVERYTHING needs a label, only stuff that might be worked on hot.

5. Related Code Sections

  • 110.21(B) – Field-applied hazard marking requirements (they love to cross-reference)
  • NFPA 70E – Referenced but not adopted by NEC; know the relationship

Typical Exam Questions:

Q: "A 200A panelboard is installed in a single-family dwelling. Does it require an arc-flash hazard marking per 110.16?"

A: NO. Dwelling units are exempt. (Easy points if you remember the "other than dwelling units" language)

Q: "An arc-flash hazard label must include all of the following EXCEPT: (A) Nominal voltage (B) Arc-flash boundary (C) Name of inspector (D) Date of assessment"

A: (C) Name of inspector. Know the four required items cold.

Q: "Arc-flash hazard markings must comply with which section regarding field marking requirements?"

A: 110.21(B). They love these cross-reference questions.


THE BOTTOM LINE

110.16 isn't just bureaucratic box-checking – it's the Code's way of saying, "Hey, we know you're going to work on this stuff hot eventually, so at least know what you're dealing with."

Arc-flash incidents are no joke. We're talking 35,000°F temperatures, copper vapor explosions, and pressures that'll blow doors off hinges. That little label is the difference between "close call at work" and "closed casket at the funeral home."

So yeah, put the damn labels on. Make sure they're accurate. Update them when the system changes. And for the love of Ohm's Law, actually READ the label before you go digging around in live gear.

Your wife, kids, and creditors want you to make it home in one piece. Don't let your last words be, "It's probably fine."

Stay safe out there, and remember: The label isn't there to protect the equipment – it's there to protect YOU.


Now go forth and label responsibly. And if you see gear without proper arc-flash markings, channel your inner safety nerd and get it fixed. Future you will thank present you.

NEC Reference: Section 110.16 · 2026 NEC (NFPA 70)

Want All 2,966 Sections?
Unlock every NEC section, 47,000+ practice questions, exam simulations, spaced-repetition flashcards, and full progress tracking. Starting at $8.33/mo.