110.33Entrance to Enclosures and Access to Working Space

Article 110GENERAL REQUIREMENTS FOR ELECTRICAL INSTALLATIONS

NEC 110.33: Entrance to Enclosures and Access to Working Space

Or: "Don't Build an Electrical Mousetrap (Because YOU'RE the Mouse)"


The Plain-Language Breakdown

Alright, listen up. This section is all about not trapping yourself inside electrical rooms like some kind of electrician-flavored bug in a jar. The Code writers looked at enough accident reports of sparky BBQ incidents and said, "Hey, maybe we should make sure people can actually GET OUT when things go sideways."

Here's what the NEC is demanding:

The Basic Door Rules (Because Hobbits Don't Work on Gear)

You need at least one entrance to your electrical room that's:

  • 24 inches wide minimum (that's two feet for those of you who still measure with your boots)
  • 6½ feet high (because basketballers need to work on panels too)

And here's the kicker: When you swing those equipment doors open, they can't block your escape route. If opening the doors narrows your exit path to less than 24 inches wide or 6½ feet high, you've just created what we professionals call "a really bad day waiting to happen."

Think about it: You're troubleshooting, something arcs and catches fire, your brain screams "GET OUT," but surprise!—the door you opened is now blocking the exit. You're doing the panic shuffle, trying to squeeze past, and your apprentice is filming for TikTok instead of helping. Don't be that guy.


Large Equipment: The "Two Doors or Extra Room" Rule

Got switchgear or control panels wider than 6 feet? Congratulations, you're now in "big boy equipment" territory, and the NEC wants entrances at BOTH ends.

UNLESS you meet one of these "get out of jail free" conditions:

Option A - The "Clear Shot to Freedom": You get a single entrance IF there's a continuous, unobstructed path out. Think of it like a hallway that leads straight to safety—no storage racks, no conduit runs blocking the aisle, no pallet of breakers that "temporarily" lives there for six months.

Option B - The "Double Your Space, Keep Your Door": You can keep a single entrance IF you provide TWICE the working clearance depth required by Table 110.34(A). And that single door? It's gotta be positioned so the distance from the equipment to the nearest edge of the entrance meets the minimum in that same table.

Translation: You're basically saying, "I only gave them one door, but I gave them a football field of space to back away from disaster." The Code is cool with that trade-off.


Guarding: Cover Your (Energized) Assets

If there are bare energized parts (at ANY voltage—yes, even 120V can kill you, smart guy) or insulated energized parts hanging out near the entrance, you better guard them.

Why? Because when someone's running out of that room like their hair's on fire (possibly literally), they shouldn't have to worry about grabbing a 480V bus bar on the way out. Guards, barriers, insulation—use whatever keeps meat from meeting voltage.


Personnel Doors: The Panic-Friendly Exit

Here's where it gets real specific. If there's a personnel door within 25 feet of the working space edge, that door needs to:

  1. Open at least 90 degrees in the direction of egress (that means OUT, toward freedom, not back into the room of doom)
  2. Be equipped with panic hardware or fire exit hardware (you know, those bars you can hip-check to open when your hands are full of "OH CRAP")

The hardware has to be listed (UL 305 for panic hardware, UL 10C for fire exit hardware). No Home Depot "looks close enough" specials.

Why? Because when the smoke alarm's screaming and you can't see your hand in front of your face, you shouldn't need to fumble for a doorknob. You should be able to body-slam that door open like a linebacker and keep moving.


Access: Ladders and Stairs (No Parkour Required)

If your electrical equipment is installed on platforms, balconies, mezzanines, attics, or roof spaces, you need permanent ladders or stairways for safe access.

"Permanent" means PERMANENT—not a borrowed extension ladder, not a milk crate tower, not "just shimmy up the conduit rack."

The Code doesn't want you doing American Ninja Warrior just to reset a breaker. Provide real access or put the equipment somewhere that doesn't require climbing gear.


Key Takeaways (The Stuff You NEED to Remember)

Minimum entrance size: 24 inches wide × 6½ feet high

Open equipment doors cannot block the exit below these minimums

Switchgear/panels over 6 feet wide = two entrances (unless you qualify for an exception)

Exception 1: Single entrance OK if there's an unobstructed exit path

Exception 2: Single entrance OK if working space is double the Table 110.34(A) requirement, AND the entrance is positioned per that table's distances

Guard all bare energized parts near entrances (at any voltage)

Doors within 25 feet: Must open 90° outward and have listed panic/fire exit hardware

Equipment on elevated surfaces: Must have permanent ladders or stairs (no Spider-Man stuff)


Real-World Jobsite Scenarios

Scenario 1: The Door That Became a Death Trap

You're working on a 480V switchgear lineup in a tight utility room. The gear is 8 feet wide, and there's only one entrance. The engineer says, "We're good—there's plenty of room."

WRONG. That gear is over 6 feet wide, so you need entrances at both ends—UNLESS you can prove:

  • There's a continuous, unobstructed exit path (nope, there's HVAC equipment blocking the back), OR
  • You've got double the working space required (you don't—you're at Code minimum)

The Fix: Add a second entrance/exit at the other end. Yes, it costs more. Yes, it's a change order. No, you don't want to explain to OSHA why someone got trapped during an arc flash event.


Scenario 2: The Swinging Door Surprise

You're in a tight electrical room. The main panel door is huge—when you open it, it takes up almost half the room. With the door open for work, the exit path is now 20 inches wide.

PROBLEM: That's less than the 24-inch minimum. The door is physically blocking your escape route below Code requirements.

The Fix: Either relocate the panel, change the door swing direction, use a smaller hinged section for access, or expand the room. You can't leave it like this.


Scenario 3: The "Just Use a Ladder, Bro" Generator

Customer wants a generator on a rooftop mezzanine. Your apprentice suggests, "We'll just bring a ladder when we need to service it."

NOPE. 110.33(B) says you need permanent access—a fixed ladder or stairway. That generator needs regular maintenance, and someday someone's going to need to get up there in a hurry.

The Fix: Install a permanent ship's ladder or stairs as part of the project scope. Budget for it up front.


Scenario 4: The Panic Door That Wasn't

You're in a data center electrical room. There's a personnel door 15 feet from the switchgear. It's got a regular keyed lockset—no panic hardware.

CODE VIOLATION. That door is within 25 feet of the working space, so it needs panic hardware or fire exit hardware, and it needs to swing 90° in the direction of egress.

The Fix: Replace with a door and hardware that meets UL 305 (panic) or UL 10C (fire exit). Yes, it's expensive. No, it's not optional.


What to Study (For Licensing Exams)

If you're cramming for your Journeyman or Master exam, focus on these testable points:

🎯 Know the minimum dimensions: 24" wide × 6½' high (they LOVE this question)

🎯 The 6-foot rule: Equipment over 6 feet wide needs two entrances (or qualifies for an exception)

🎯 The two exceptions to the two-entrance rule:

  • Unobstructed exit route
  • Double working space per Table 110.34(A)

🎯 The 25-foot rule: Doors within 25 feet need panic hardware and must swing 90° out

🎯 Permanent access required for elevated equipment (no temporary ladders)

🎯 Open doors can't restrict the exit below 24" × 6½'

Exam Tip: They often give you a scenario with large switchgear and ask if one entrance is acceptable. You'll need to determine if either exception applies. Know Table 110.34(A) working space requirements cold—you'll need them to calculate the "double space" exception.

Calculation Question Alert: Expect questions like: "You have 15kV switchgear, Condition 2. The working space is 5 feet deep. Can you use a single entrance?" (Answer: No—Table 110.34(A) requires 4 feet for that setup, so you'd need 8 feet to qualify for the single-entrance exception.)


The Bottom Line

110.33 exists because electricity doesn't care about your exit strategy—but the Code does.

Give yourself room to work, give yourself room to escape, and for the love of all that's holy, don't block your own exits. When things go wrong in an electrical room, they go wrong FAST. You need to be able to get out in the dark, in the smoke, in a panic, possibly while on fire.

This isn't about being paranoid—it's about going home with the same number of fingers, eyes, and heartbeats you showed up with.

Now go forth and leave yourself an escape route. Your future self will thank you.


Remember: The NEC is written in blood. Every rule exists because somebody didn't make it home. Don't be the reason they add another section.

NEC Reference: Section 110.33 · 2026 NEC (NFPA 70)