Article 110GENERAL REQUIREMENTS FOR ELECTRICAL INSTALLATIONS

NEC 110.76: Access to Vaults and Tunnels

Or: "How Not to Trap People Underground Like a Horror Movie"


THE PLAIN-LANGUAGE BREAKDOWN

Alright, gather 'round. We're talking about vaults and tunnels today—and no, not the kind where Batman keeps his cool cars. We're talking about those electrical vaults and underground tunnels that make you feel like you're entering the bowels of a building. The ones where you're thinking, "If something goes sideways down here, I'm either turning into a crispy critter or I'm stuck until the janitor finds me next Thursday."

Part (A) - Location: Don't Be a Cartoon Villain

Here's the deal: When you're putting in access hatches for people to climb through, DO NOT put them directly over live electrical equipment or conductors. Why? Because Murphy's Law is real, my friend. The minute someone drops a screwdriver, a flashlight, or—God forbid—themselves through that opening, you want them landing on concrete, not on a 15kV bus.

Think of it like this: You wouldn't put a manhole cover directly over a beehive, would you? Same principle.

However—and this is important—you can put other types of openings over equipment if you need to get gear in and out. That 2,000-pound transformer isn't walking itself down the ladder, so yeah, you need a way to lower it in. Just don't make that the same hole Larry uses to climb down for his Monday morning rounds.

Part (B) - Locks: The "Don't Pull a Edgar Allan Poe" Rule

Now let's talk about locks, because apparently, at some point in electrical history, someone thought it was a great idea to lock people inside vaults. Maybe it was an accident. Maybe it was Carl from accounting settling a grudge. Either way, the Code now says: Nope. Not on my watch.

Here's what you need to know:

  1. If someone's inside, they can ALWAYS get out—even if some joker locks the door from the outside
  2. For padlock situations (the most common setup), you need to rig it so the padlock can snap onto the hasp without actually locking anybody in

Picture this: You're inside doing a transformer inspection. Your apprentice—bless his heart, he's trying—closes the door behind you and clicks the padlock shut "for security." If your setup is Code-compliant, that padlock prevents the door from being locked from the outside, but you can still open it from the inside. You're not stuck. You don't have to eat the granola bar in your lunch pail and wait for rescue.

It's basically a "panic bar" concept for underground spaces. You need an "oh crap" exit strategy.


KEY TAKEAWAYS (The Stuff That Matters)

🔧 Access openings for personnel CANNOT be directly above energized equipment or conductors

🔧 Equipment access openings (for installing/removing gear) CAN be over equipment—different purpose, different rules

🔧 Interior occupants must ALWAYS be able to exit, even when locked from outside

🔧 Padlock arrangements must allow the lock to close without actually locking people inside

🔧 This is in addition to 110.34 requirements—not instead of (if applicable)


REAL-WORLD SCENARIOS (Tales from the Trenches)

Scenario 1: The Manhole Mishap

You're doing a vault installation at a downtown high-rise. The engineer's drawings show the personnel access hatch centered in the room—right over the 480V switchgear. Beautiful symmetry, terrible idea.

You call it out. The engineer gets snippy: "That's the most convenient location!"

You: "Sure, until someone's climbing down with a tool belt and drops a Klein 11-in-1. Then we're all watching the fireworks show, and I'm filling out incident reports until retirement."

Solution: Move the access opening to the side. Equipment stays where it is, access point moves to a safe zone. Everybody goes home with their eyebrows intact.

Scenario 2: The Padlock Predicament

You're working in a utility vault that's been there since Nixon was president. The setup has a regular padlock on the outside. You go down to do some testing, door closes, and you hear click. Your partner accidentally locked you in while securing the site.

If this vault is compliant, that padlock closed onto a hasp setup that doesn't actually engage the locking mechanism from your side. You push the door, it opens, and you climb out. You give your partner the stink-eye, but you're not calling 911.

If it's not compliant? You're down there until someone notices you're missing. Hope you brought a book.

Scenario 3: The Equipment Elevator

You're replacing a 3,000-pound transformer in an underground vault. You need to drop it through the ceiling. The inspector says, "Hey, your access opening is over the equipment! Violation!"

You: "Hold up—110.76(A) says 'access openings for personnel' can't be over equipment. This is an equipment installation opening. Different animal. We're not sending Larry down through here on Tuesdays; we're threading a transformer on a come-along."

Inspector checks the Code, grumbles, and moves on. You win this round.


WHAT TO STUDY (Exam Prep Gold)

If you're testing for your license, here's what they love to ask:

📝 The difference between personnel access openings and equipment access openings—they'll try to trick you with scenarios

📝 The interior exit requirement—expect a question about locked doors and emergency egress

📝 The padlock setup—they'll describe a locking arrangement and ask if it's compliant

📝 Where access openings can and cannot be located—usually a diagram-based question

📝 The reference to 110.34—know that vault access has to comply with BOTH sections when applicable

Sample Question You'll See:

"A personnel access opening to an electrical vault is located directly above a 15kV bus. The opening is used monthly for inspections. Is this compliant with NEC 110.76(A)?"

Answer: Hell no. Personnel access openings can't be directly over electrical equipment or conductors. Move it to the side, chief.


THE BOTTOM LINE

Look, vaults and tunnels are sketchy enough without adding unnecessary danger or the possibility of getting locked in like you're in a Saw movie. The Code wants two things:

  1. Don't put people directly over energized equipment when they're climbing in and out
  2. Make sure people can always escape, even if someone screws up the lock situation

Follow these rules, and everybody goes home safe. Ignore them, and you're one accident away from being a cautionary tale at the next OSHA 30-hour class.

Now go forth and design your vaults like you give a damn about the poor souls who'll be working in them for the next 50 years. Future you will thank present you.

Stay safe, stay smart, and for the love of all that's holy—don't lock your coworkers underground.

NEC Reference: Section 110.76 · 2026 NEC (NFPA 70)